Steel
Free Surface
Other free surfaces at request. | Dampers available for manual or automatic use.
Damper
- The energy saver in data centers.
- Regulates free surface from 0% to 39%.
- Avoids unnecessary leakage.
- Manual setting via mechanical device.
- Automatic setting via setpoints for pressure or temperature.
Covering
Steelpanels can be Powdercoated, Galvanized and silver passivated. Covered with any elastic, textile or HPL coverings.
Substructure
Admeasurement | 600 x 600 mm |
Pedestals material | Stahl verzinkt |
Heights (without cover) | ~ 70 – 2000 mm |
Recommended use | Generally recommended: stringer from floor height > 500 mm |
Electro static
(Depends on system and material) | > 10E5 Ω |
Load bearing capacity
Point load rated after DIN EN 12825 | Klasse 3 – 6 |
Nominal load | 3 kN – 7 kN |
Ultimate load | ≥ 6 kN – 14 kN |
Safety factor | ≥ 2,0 |
Building material class
acc. to DIN 4102 T1 | A1 |
Panel
Admeasurement | 600 x 600 mm |
Thickness (without cover) | 28 – 44 mm |
System weight (without cover, floor height 1000 mm) | 30 – 45 kg/m² |
Panel weight | 10 – 15 kg/piece |
Material | Steel, powder coated |