HydroLogic Panel V

Hydrologic Panel V

Consisting of two heat exchangers and four EC-fans with a free cross section of 44%, the panels can be placed in the hot or cold aisle, pulling or pushing the air.

Certified according to DIN EN 12825 for load capacities of 3 – 5 kN.

To avoid static charges the raised floor panels are coated with conductive powder.

Existing fl oors can quickly, easily and fl exibly be changed.

Depending on the spread of the fl ow temperature on water and air side, benefi ts up to 50 kW are possible.

The panel is also available as direct evaporator version.

The fans react automatically on temperature changes in server cabinets and lower or raise the volume of air in dependence of preset temperature values.

The regulation of the Hydrologic V plate is done individually using the built-in control.

The Hydrologic Panel can be equipped with the same coverings as the rest of the raised floor.

Wassergekühlte Doppelbodenplatte

3D View

We have prepared a interactive 3D model. You can take a closer look at a Hydrologic Panel here.

Technical Data

Performance

Cooling capacity
40 kW
Voltage
230 V
Power consumption
720 W
Spread water
12°C/18°C
Water volume
5,5 m³/h
Zulufttemperatur Server
21° – 30°C
Water connector
1/2‘‘
Max Pressure
16 bar
Pressure loss
1 bar max
Cooling media
Water or glycole water mix

Panel

Admeasurement
600 x 1200 mm
Thickness
535 mm, without cover
Topside
PVC, HPL, rubber
Bottomside
4 x EC-Fan
Weight
80 kg
Material
Powder-coated steel
Building material class
A1
Free air outlet
44%
Resistance to ground
< 10⁸ Ohm (Depends on coverings)

Load bearing capacity

Point load
3kN
Ultimate load
<6kN
Heights
600-2000 mm